| Standby kVA | 900 kVA |
| Standby kW | 720 kW |
| Standby Current | 1299 A |
| Prime kVA | 800 kVA |
| Prime kW | 640 kW |
| Prime Current | 1155 A |
| Frequency | 50 Hz |
| Voltage | 400/230V, 3-Phase |
| Power Factor | 0.8 lagging |
| Make & Model | Perkins 4006-23TAG3A |
| Cylinders | 6 In-Line |
| Displacement | 22.92 Liters |
| Bore & Stroke | 160 × 190 mm |
| Aspiration | Turbocharged & Aftercooled |
| Compression Ratio | 13.6:1 |
| Make & Model | Leroy Somer TAL-049-C |
| Options | Stamford HCI634G / Mecc Alte ECO46-2S |
| AVR | Digital R450 |
| Voltage Regulation | ±1% |
| Controller | Auto Mains Failure (AMF) |
| Controller Model | DSE 7320 MKII Co |
| Fuel Tank | 1400 Liters |
| Runtime @ 100% Prime | 8.1 Hours |
| Cooling | Water-Cooled, Radiator Mounted |
| Max Ambient | 40°C |
| Coolant Capacity | 105 L |
| Oil Capacity | 113.4 L |
| Open Frame (L×W×H) | 4100×1750×2210 |
| Open Frame Weight | 4800 kg |
Enclosure, ATS, fuel system and controls configured to your specification.