KDN-P1650 KORDEN diesel generator
KORDEN · Diesel Generator Set

KDN-P1650

1650 kVA standby diesel generator set. Powered by Perkins 4012-46TAG2A with Leroy Somer LL8224N and Auto Mains Failure (AMF) control — supplied, installed, tested and commissioned.

Standby
1650
kVA · 1320 kW
Prime
1506
kVA · 1200 kW
Voltage
400/230V, 3-Phase
50 Hz · PF 0.8 lagging
Technical Specification

Power Ratings

Standby kVA1650 kVA
Standby kW1320 kW
Standby Current2382 A
Prime kVA1506 kVA
Prime kW1200 kW
Prime Current2174 A
Frequency50 Hz
Voltage400/230V, 3-Phase
Power Factor0.8 lagging

Engine

Make & ModelPerkins 4012-46TAG2A
Optional EngineCummins KTA50-G8
Cylinders12-Cyl Vee
Displacement45.8 Liters
Bore × Stroke160 × 190 mm
AspirationTurbocharged & Aftercooled

Alternator

Make & ModelLeroy Somer LL8224N
OptionsStamford HCI634K / Mecc Alte ECP50-2VL
AVRDigital R450
Voltage Regulation±1%

Control & Fuel

ControllerAuto Mains Failure (AMF)
Controller ModelDSE 7320 MKII Co
Fuel Tank2350 Liters L
Runtime @ 75%10.4 Hours
CoolingWater-Cooled, Radiator Mounted
Max Ambient40°C

Dimensions & Weight

Open Frame (L×W×H)4850×1908×2440
Open Frame Weight10181 kg
Silent Canopy (L×W×H)12192×2438×2896
Silent Canopy Weight21580 kg

Configure the KDN-P1650 for your project

Enclosure, ATS, fuel system and controls configured to your specification.