KDN-P135 KORDEN diesel generator
KORDEN · Diesel Generator Set

KDN-P135

165 kVA standby diesel generator set. Powered by Perkins 1106A-70TAG2 with Leroy Somer FGL30080 and Auto Mains Failure (AMF) control — supplied, installed, tested and commissioned.

Standby
165
kVA · 132 kW
Prime
148
kVA · 118 kW
Voltage
400/230V, 3-Phase
50 Hz · PF 0.8 lagging
Technical Specification

Power Ratings

Standby kVA165 kVA
Standby kW132 kW
Standby Current238 A
Prime kVA148 kVA
Prime kW118 kW
Prime Current214 A
Frequency50 Hz
Voltage400/230V, 3-Phase
Power Factor0.8 lagging

Engine

Make & ModelPerkins 1106A-70TAG2
Optional EngineCummins 6CTAA8.3-G7
Cylinders6 In-Line
Displacement7.01 Liters
Bore × Stroke105 × 135 mm
AspirationTurbocharged

Alternator

Make & ModelLeroy Somer FGL30080
OptionsStamford UCI274D / Mecc Alte ECO38-2S
AVRDigital R450
Voltage Regulation±1%

Control & Fuel

ControllerAuto Mains Failure (AMF)
Controller ModelDSE 7320 MKII Co
Fuel Tank161 Liters L
Runtime @ 75%7.1 Hours
CoolingWater-Cooled, Radiator Mounted
Max Ambient40°C

Dimensions & Weight

Open Frame (L×W×H)2450×1010×1544
Open Frame Weight1320 kg
Silent Canopy (L×W×H)3200×1100×1800
Silent Canopy Weight2060 kg

Configure the KDN-P135 for your project

Enclosure, ATS, fuel system and controls configured to your specification.