| Standby kVA | 1125 kVA |
| Standby kW | 900 kW |
| Standby Current | 1624 A |
| Prime kVA | 1012 kVA |
| Prime kW | 810 kW |
| Prime Current | 1461 A |
| Frequency | 50 Hz |
| Voltage | 400/230V, 3-Phase |
| Power Factor | 0.8 lagging |
| Make & Model | Perkins 4008-TAG2A |
| Optional Engine | Cummins KTA38-G5 |
| Cylinders | 8-Cyl Vee |
| Displacement | 30.561 Liters |
| Bore × Stroke | 160 × 190 mm |
| Aspiration | Turbocharged & Aftercooled |
| Make & Model | Leroy Somer TAL049E |
| Options | Stamford HCI634H / Mecc Alte ECO46-3L |
| AVR | Digital R450 |
| Voltage Regulation | ±1% |
| Controller | Auto Mains Failure (AMF) |
| Controller Model | DSE 7320 MKII Co |
| Fuel Tank | 1400 Liters L |
| Runtime @ 75% | 10.8 Hours |
| Cooling | Water-Cooled, Radiator Mounted |
| Max Ambient | 40°C |
| Open Frame (L×W×H) | 4788×2046×2419 |
| Open Frame Weight | 7032 kg |
| Silent Canopy (L×W×H) | 6058×2438×2591 |
| Silent Canopy Weight | 12590 kg |
Enclosure, ATS, fuel system and controls configured to your specification.